NF F 16-101/IEC 60695-2-11:2000 Glow-wire flammability test
1.Standard--- NF F 16-101/IEC 60695-2-11:2000
IEC 60695-2-11: Glawing/hot wire based test methods-Glow-wire flammability test method for end-products.
The standards replace NF C 20-455
2.Scope-- NF F 16-101/IEC 60695-2-11:2000
This standard generally used for small-size material (final product) of the combustion properties of the test.
NF F 16-101:1988 referenced in this standard (IEC 60695-2-11) and EN ISO 4589-2 for I-level oxygen index test.
According to IEC 60695-2-11 and EN ISO 4589-2 two test results, I assess the level of oxygen that level I0-I4 five levels (I0, I1, I2, I3, I4).
Class |
Result of Tests |
O.I. |
Glow wire |
I0 |
≥70 |
No ignition at 960℃ |
I1 |
≥45 |
No ignition at 960℃ |
I2 |
≥32 |
No ignition at 850℃ |
I3 |
≥28 |
Ignition does not persist at 850℃ after glow wire is withdrawn |
I4 |
≥20 |
|
NC(1) |
<20 |
|
NC(1): Non-classified |
Glow wire apply the test temperature is 850 ℃ and 960 ℃
3.Other standard--- NF F 16-101/IEC 60695-2-11:2000
IEC 60695-2-Fire hazard testing-Part 2: Glawing/hot wire based test methods, consists of the following parts:
IEC 60695-2-10: Glawing/hot wire based test methods-Glow-wire apparatus and common test procedure.
IEC 60695-2-11: Glawing/hot wire based test methods-Glow-wire flammability test method for end-products.
IEC 60695-2-12: Glawing/hot wire based test methods-Glow-wire flammability test method for materials.
IEC 60695-2-13: Glawing/hot wire based test methods-Glow-wire ignitability test method for materials.
(+86)025-8658 3475 |