Home   Construction materials   ISO EN 1182 Non-combustibility test
 

ISO EN 1182 Non-combustibility test

ISO EN 1182 Non-combustibility test

 

ISO EN 1182:2002 Non-combustibility test method of building materials

The standard is similar with GB/T 5464:1999

 

1. Scope

This method of test for determining the non-combustibility performance, under specified conditions, of homogeneous building products and substantial components of non-homogeneous building products. The test is relevant for the classes A1A2Af1Af2.

 

2. Test method

The specimen is weighted and placed into a basket. A thermocouple is inserted into the centre of the specimen and connected to the logging equipment. In addition the specimen thermocouple, there is also a thermocouple placed inside of the furnace. The specimen is lowered into the furnace (which is set at 750°C) and remains in this position for the entire 20 minute test duration. During the test the temperatures from the two thermocouples are logged and observations relating to the duration of flaming are recorded.

 

3. Test specimen

The test specimen shall be cylindrical and each shall have a volume of (76±8) cm3, a diameter of 45(+0/-2) mm and a height of (50±3) mm. eight specimens are required.

 

4. Expression of results

 

4.1 Mass loss

Calculate and record the mass loss in % for each of the specimens, expressed as a percentage of the initial mass of the specimen.

 

4.2 Flaming

Calculate and record the total duration of sustained flaming, in s, for each of the specimens.

 

4.3 Temperature rise

Calculate and record the temperature rise, T=Tm-Tf, in , for each of the specimens recorded by the thermocouple. The temperature rise, in , shall be calculated from the temperatures recorded by the two thermocouples for each specimen as follow:

a)      specimen centre thermocouple

Tc=Tc (max)-Tc (final)

b)  specimen surface thermocouple

       Ts=Ts (max)-Ts (final)

 

Firete.com focus on BS6853, NFF16-101, DIN5510-2, NFPA130, EN45545-2, EN13501-1

 

Tel: (+00 86) 25-8658 3475


 Source:防火网  Addtime:9/2/2010 Hits:14854