Home station  
Set as homepage Add to favorites    中文版 繁体 English
 
Testing to: Rolling Fire testing | Building Fire testing | Marine material | Aircraft material | Fire Resistance | Jet Fire | Other
   
User name:
Password:
Code:
   
Fire standard
RailwayMarineBusBuilding
Test method More>>
BS 476-6:1989+A1:2009 fire...
BS 476-7:1997 Classificati...
BS 476-20:1987 fire resist...
BS ISO 4589-2:2006-06
NF P 92-501: M classificat...
NF P 92-503: M classificat...
NF P 92-504: Speed of spre...
ASTM E 662: Smoke density ...
ASTM E 648 Flooring test
ASTM E 162: surface flamma...
 
Home   Popular Standard   BS 6853/BS 476-7: Classification of spread of flame
 

BS 6853/BS 476-7: Classification of spread of flame

BS 6853/BS 476-7: Classification of spread of flame

BS 476-7: Fire tests on building materials and structures-Part 7 method of test to determine the classification of the surface spread of flame of products.

 

BS 6853/BS 476-7 test method

The specimen is mounted in a water-cooled holder and is exposed to a radiant panel over a ten minute test duration. In addition, a pilot flame is applied to the bottom corner of the specimen during the first minute of test. The time required for the flame front to reach reference marks on the specimen is noted, together with the extent of flame spread at one minute thirty seconds test duration and at the end of the test. Observations are also made of the burning behaviour.

 

Materials are classified according to test performance as shown in the table below. Class 1 is the best classification that can be achieved during this test alone and Class 4 is the worst classification that can be achieved on this test. Class 4 materials are considered high risk.

 

BS 6853/BS 476-7:1997 classification Evaluate

Classification of spread of flame

Classification

Spread of flame at 1.5 min

Final spread of flame (10 min)

Limit  (mm)

Limit for one specimen in sample   (mm)

Limit  (mm)

Limit for one specimen in sample  (mm)

Class 1

165

165+25

165

165+25

Class 2

215

215+25

455

455+45

Class 3

265

265+25

710

710+75

Class 4

Exceeding the limits for class 3

 

BS 6853:1999 standard requirement

Worst Classification requirement: Class 2, allows Classification: Class 1 or Class 2

 

(+86) 025-8658 3475


 Source:防火网  Addtime:10/18/2010  Hits:3311

 Previous : BS 6853/BS 476-6:1989+A1:2009 fire propagation

 Next: NF F 16-101/ EN ISO 4589-2 Ambient-temperature oxygen index test
 
 
Home | Fire Test & Certification | Standard | News | Product | Exhibition | Flame retardant | On-line consultation | Contact us
Copyright © 2008-2024 Firete.com All Right Reserved
TEL:(+86)-25-8658 3475