Home   Germany   DIN EN 60332-1-2:2004 vertical flame propagation for a single insulated wire or cable
 

DIN EN 60332-1-2:2004 vertical flame propagation for a single insulated wire or cable

DIN EN 60332-1-2:2004 vertical flame propagation for a single insulated wire or cable

DIN EN 60332-1-2:2004 Tests on electric and optical fibre cables under fire conditions—Part 1-2: Test for vertical flame propagation for a single insulated wire or cable—Procedure for 1 KW pre-mixed flame and is for general use, except that the procedure specified of less than 0.5mm2 total cross-section because the conductor melts before the test is completed, or for the testing of small optical fibre cables because the cable is broken before the test is completes. In these cases, the procedure giver in DIN EN IEC 60332-2-2 is recommended.

 

Description of test method

The test sample shall be a piece of single insulated conductor or cable (600± 25)mm long.

The single insulated conductor or cable shall pass the test if the distance between the lower edge of the top support and the onset of charring is greater than 50 mm.

In addition, a failure shall be recorded if charring extends downwards to a point greater than 540 mm from the lower edge of the top support.

If a failure is record, two more tests shall be carried out ,if both tests result in passes, the single insulated conductor or cable shall be deemed to have passed the test.

Other standard:

DIN EN 60332-2-2:2004 Tests on electric and optical fibre cables under fire conditions Part 2-2: Tests for vertical flame propagation for a single small insulated wire or cable procedure for diffusion flame.


 Source:防火网  Addtime:9/2/2010 Hits:3926

 Previous: DIN EN 60695-11-10: 50W horizontal and vertical flame test methods

 Next: EN 50399: common test methods for cables under fire conditions
 
 
Home | Fire Test & Certification | Standard | News | Product | Exhibition | Flame retardant | On-line consultation | Contact us
Copyright © 2008-2024 Firete.com All Right Reserved
TEL:(+86)-25-8658 3475