Home   Rolling Fire testing   BS 6853/BS 476-7: Classification of spread of flame
 

BS 6853/BS 476-7: Classification of spread of flame

BS 6853/BS 476-7: Classification of spread of flame

 

BS 476-7: Fire tests on building materials and structures-Part 7 method of test to determine the classification of the surface spread of flame of products.

 

BS 6853 / BS 476-7 test method

 

The specimen is mounted in a water-cooled holder and is exposed to a radiant panel over a ten minute test duration. In addition, a pilot flame is applied to the bottom corner of the specimen during the first minute of test. The time required for the flame front to reach reference marks on the specimen is noted, together with the extent of flame spread at one minute thirty seconds test duration and at the end of the test. Observations are also made of the burning behaviour.

 

Materials are classified according to test performance as shown in the table below. Class 1 is the best classification that can be achieved during this test alone and Class 4 is the worst classification that can be achieved on this test. Class 4 materials are considered high risk.

 

BS 6853 / BS 476-7:1997 classification Evaluate

 

Classification of spread of flame

Classification

Spread of flame at 1.5 min

Final spread of flame (10 min)

Limit  (mm)

Limit for one specimen in sample   (mm)

Limit  (mm)

Limit for one specimen in sample  (mm)

Class 1

165

165+25

165

165+25

Class 2

215

215+25

455

455+45

Class 3

265

265+25

710

710+75

Class 4

Exceeding the limits for class 3

 

BS 6853:1999 standard requirement

 

Worst Classification requirement: Class 2, allows Classification: Class 1 or Class 2

 

Tel: (+0086) 25-8658 3475  Tel: (+0086) 400-666-7290


 Source:防火网  Addtime:12/15/2010 Hits:3263

 Previous: BS 6853/BS 476-6:1989+A1:2009 fire propagation

 Next: EN 13501-1:2007+A1+2009 Classification using data from reaction to fire tests
 
 
Home | Fire Test & Certification | Standard | News | Product | Exhibition | Flame retardant | On-line consultation | Contact us
Copyright © 2008-2024 Firete.com All Right Reserved
TEL:(+86)-25-8658 3475