BS 8434-1 Methods of test for assessment of the fire integrity of electric cables - Part 1: Test for unprotected small cables for use in emergency circuits-BS EN 50200 with addition of water spray BS 8434-1 電纜防火完整性評估的測試方法。第1部分:應急電路中使用的未保護小電纜的測試-BS EN 50200外加噴水器。
BS 8434-2 Methods oftest for assessment of the fire integrity of electric cables - Part 2: Test for unprotected small cables for use in emergency circuits- BS EN 50200 with a 930 °Cflame and with water spray BS 8434-2 電纜防火完整性評估的測試方法,第2部分:應急電路中使用的無防護型小電纜的測試-BS EN 50200外加930°C火焰和噴水器。
BS EN 50200, Method of test for resistance to fire of unprotected small cables for use in emergency circuits. BS EN 50200,應急電路中未保護的小電纜的防火性測試方法。
√ BS 8434-2電纜著火條件完整性-標準適用範圍
BS 8434-2該標準規定了一種用於小型無保護電纜的測試方法,其中BS EN 50200的要求被修改為使用(930+40)C的火焰溫 度和噴水的應用。使用此方法證明符合BS 5839-1要求。 This British Standard specifies a method of test to be used for small unprotected cables where the requirements of BS EN 50200 are modified to use a flame temperature of (930+40)'C and the application of water spray. Compliance with the requirements of BS 5839-1:2002, 26.2e) may be demonstrated using this method
√ BS EN 50200緊急電路用無保護小電纜的耐火性試驗方法
EN 50200定義了用於應急電路的無保護小電纜(最大20mm)的耐火性測試方法。測試方法為在實驗室中安裝長度為1200mm的電纜樣品,測試期間線芯的標稱值為施加電壓,從而產生閉合電路。 在測試期間,電纜在常規溫度842°Cand機械衝程下經受特定時間段的火焰作用。 電纜正常運行的測量時間對應於所謂的耐火等級PH,這在標準NP-B-02851-1中也有提到 - 建築構件的耐火試驗(外徑不大的細線的試驗方法) 小於20毫米)。
√ BS EN 50200測試持續時間以分鐘表示,並記錄在以下分類中
PH 15: Flame exposure for 15 minutes PH 30: Flame exposure for 30 minutes PH 60: Flame exposure for 60 minutes PH 90: Flame exposure for 90 minutes PH 120: Flame exposure for 120 minutes
EN 50200附錄E還有噴水(火災,機械衝擊和噴水),這是引用BS 8434-1標準的。 EN 50200與IEC 60331-2類似。與BS 6387不同的是,EN 50200測試同一根樣品,同時受到火焰作用、機械衝擊和水噴霧的應力。