EN 50266-2-4: Common test methods for cable under fire condition—Test for vertical flame spread of vertically-mounted bunched wires or cables –Part 2-5:  Procedures –Category C  
EN 50266-2-4: 著火條件下電纜的通用試驗方法-多根成束垂直火焰燃燒-第2-5部分-類型C 
  
EN 50266-2-4 together with BS EN 50266-1, EN 50266-2-1, EN 50266-2-2, EN 50266-2-3 and EN 50266-2-5, it supersedes BS 4066-3:1994 which is withdrawn  
 
DIN 50266-2-4 類型C 是針對電纜直徑大於等於12mm的測試,整個測試時間為20分鐘。樣品的前端固定。根據樣品燃燒後的破壞長度來評估樣品是否通過DIN EN 50266-2-4此項測試。 
 
電線電纜其他標準 : 
 
EN 50266-1 common test methods for cables under fire conditions—Test for vertical flame spread of vertically-mounted bunched wired or cables-Part 1: apparatus. 著火條件下電纜的通用試驗方法-多根成束垂直火焰燃燒-第1部分-設備裝置 
 
EN 50266-2-5 Common test methods for cable under fire condition—Test for vertical flame spread of vertically-mounted bunched wires or cables –Part 2-5: Procedures –Small cables-Category D 著火條件下電纜的通用試驗方法-多根成束垂直火焰燃燒-第2-5部分-小型電纜-類型D. 
 
DIN EN 50266-2-4電線電纜多根成束垂直火焰燃燒(電纜直徑≥12mm),需要進行此測試的電纜和導線(不包括資料線),燃燒測試後電纜的最大破壞長度不超過2.5m. 
 
DIN EN 50305 section 9.1.1電線電纜多根成束垂直火焰燃燒(6mm<電纜直徑<12mm) 需要進行此測試的電纜和導線(不包括資料線),燃燒測試後電纜的最大破壞長度不超過2.5m. 
 
DIN EN 50305 section 9.1.2電線電纜多根成束垂直火焰燃燒(電纜直徑≤6mm 需要進行此測試的電纜和導線(不包括資料線),燃燒測試後電纜的最大破壞長度不超過2.5m. 
 
DIN EN 60332-1-2電線電纜單根垂直火焰燃燒,需要進行此測試的電纜和導線,包括資料線(光纖電纜、資料匯流排導線、同軸電纜),燃燒測試後,電纜的上端破壞長度不超過50mm,下端不超過540mm. 
 