首页   美国   ASTM C692评定奥氏体不锈钢热绝缘材料对外部应力腐蚀开裂趋势影响标准试验方法
 

ASTM C692评定奥氏体不锈钢热绝缘材料对外部应力腐蚀开裂趋势影响标准试验方法

ASTM C692 Standard Test Method for Evaluating the Influence of Thermal Insulations on External Stress Corrosion Cracking Tendency of Austenitic Stainless Steel
ASTM C692 评定奥氏体不锈钢热绝缘材料对外部应力腐蚀开裂趋势影响标准试验方法

An inherent characteristic of some alloys of austenitic stainless steel is their tendency to crack at stress points when exposed to certain corrosive environments. The mechanisms of ESCC are complex and not completely understood but are apparently related to certain metallurgical properties. Chloride ions concentrated at a stress point will catalyze crack formation. It has been reported that other halide ions do not promote ESCC to the same degree as does chloride using the test technology of Test Method C692 (drip test).
Chlorides are common to many environments, so great care shall be taken to protect austenitic stainless steel from chloride contamination.
Most thermal insulations will not, of themselves, cause stress corrosion cracking as shown by qualification tests. When exposed to elevated-temperature (boiling point range), environments containing chlorides, moisture, and oxygen, however, some insulation systems act as collecting media, transmigrating and concentrating chlorides on heated stainless steel surfaces. If moisture is not present, the chloride salts cannot migrate, and stress corrosion cracking because of chloride-contaminated insulation cannot take place.
Insulation materials are available that are specially formulated to inhibit stress corrosion cracking in the presence of chlorides through modifications in basic composition or incorporation of certain chemical additives.
The ability of the 28-day test to measure the corrosion potential of insulation materials is documented by Karnes, whose data appear to have been used for construction of the acceptability curve used in Specification C795 and other specifications.
The metal for all of the coupons used in this test method (C692) shall be qualified (see Section 14) to ascertain that under conditions of the test, chloride ions will cause the metal to crack, and deionized water alone will not cause cracks.

1. Scope
1.1 This test method covers two procedures for the laboratory evaluation of thermal insulation materials to determine whether they contribute to external stress corrosion cracking (ESCC) of austenitic stainless steel due to soluble chlorides within the insulation. This laboratory procedure is not intended to cover all of the possible field conditions that contribute to ESCC.
1.2 While the 1977 edition of this test method (Dana test) is applicable only to wicking-type insulations, the procedures in this edition are intended to be applicable to all insulating materials, including cements, some of which disintegrate when tested in accordance with the 1977 edition. Wicking insulations are materials that wet through and through when partially (50 to 75 %) immersed in water for a short period of time (10 min or less).
1.3 These procedures are intended primarily as a preproduction test for qualification of the basic chemical composition of a particular manufacturer's product and are not intended to be routine tests for ongoing quality assurance or production lot compliance. Test Methods C871, on the other hand, is used for confirmation of acceptable chemical properties of subsequent lots of insulation previously found acceptable by this test method.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

2. Referenced Documents (purchase separately)
ASTM Standards
ASTM A240/A240M Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A370 Test Methods and Definitions for Mechanical Testing of Steel Products
ASTM C168 Terminology Relating to Thermal Insulation
ASTM C795 Specification for Thermal Insulation for Use in Contact with Austenitic Stainless Steel
ASTM C871 Test Methods for Chemical Analysis of Thermal Insulation Materials for Leachable Chloride, Fluoride, Silicate, and Sodium Ions
ASTM G30 Practice for Making and Using U-Bend Stress-Corrosion Test Specimens
Index Terms
austenitic stainless steel; chloride; Dana test; Drip test; external stress corrosion cracking (ESCC); qualification test; thermal insulation; wicking insulation; Austenitic stainless steel thermal insulation; Corrosion--insulating materials; Corrosion--stress-corrosion; Cracking--insulation; External stress corrosion cracking (ESCC); Stainless steel (corrosion testing); Stress corrosion cracking (SCC); Wicking ;

更多防火阻燃测试认证,请咨询中国防火网
电话:400-666-7290
网址:www.firete.com
邮箱:info@firete.com

...
 


 来源:防火网 发布时间:12/25/2013 点击次数:1441

 上一条: ASTM C689未燃烧粘土的断裂模系数测试方法标准

 下一条: ASTM C726屋面用矿物纤维绝缘板标准规范
 
 
网站首页 | 测试服务 | 各国标准 | 新闻资讯 | 防火材料 | 会展信息 | 认证服务 | 在线咨询 | 联系我们
Copyright © 2009-2024 Firete.com All Right Reserved 苏公网安备 32010502010088号
服务热线:025-86583475   备案号:苏ICP备10201999号-1 DIN5510-2 DIN5510 防火网博客