ASTM C591 Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation ASTM C591 非表面加工的硬质蜂窝状聚氨基甲酸乙酯绝热材料的标准规范 This specification covers the types, physical properties, and dimensions of unfaced, preformed rigid cellular polyurethane modified polyisocyanurate plastic material intended for use as thermal insulation on surfaces. This insulation can be classified into six types according to its compressive resistance: Types I, IV, II, III, V, and VI. Also this insulation can be classified as Grades 1 and 2 according to its service temperature range. The thermal insulation is produced by the polymerization of polymeric polyisocyanates in the presence of polyhydroxyl compounds, catalysts, cell stabilizers, and blowing agents. Different test methods shall be performed in order to determine the thermal insulation's following properties: density, compressive resistance, apparent thermal conductivity, hot-surface performance, water absorption, water vapor permeability, dimensional stability, closed-cell content, surface bearing characteristics, tensile strength, and leachable chloride, fluoride, silicate, and sodium ions. This abstract is a brief summary of the referenced standard. It is informational only and not an official part of the standard; the full text of the standard itself must be referred to for its use and application. ASTM does not give any warranty express or implied or make any representation that the contents of this abstract are accurate, complete or up to date.
1. Scope 1.1 This specification covers the types, physical properties, and dimensions of unfaced, preformed rigid cellular polyisocyanurate plastic material intended for use as thermal insulation on surfaces from -297°F (-183°C) to 300°F (149°C). For specific applications, the actual temperature limits shall be agreed upon by the manufacturer and purchaser. 1.2 This specification only covers “polyurethane modified polyisocyanurate” thermal insulation which is commonly referred to as “polyisocyanurate” thermal insulation. This standard does not encompass all polyurethane modified materials. Polyurethane modified polyisocyanurate and other polyurethane materials are similar, but the materials will perform differently under some service conditions. 1.3 This standard is designed as a material specification, not a design document. Physical property requirements vary by application and temperature. At temperatures below -70°F (-51°C) the physical properties of the polyisocyanurate insulation at the service temperature are of particular importance. Below -70°F (-51°C) the manufacturer and the purchaser must agree on what additional cold temperature performance properties are required to determine if the material can function adequately for the particular application. 1.4 The main body of this standard addresses requirements of unfaced preformed rigid cellular polyisocyanurate thermal insulation manufactured using blowing agents with an ozone depletion potential of 0 (ODP 0). 1.5 The table in the Annex A1 addresses requirements of unfaced preformed rigid cellular polyisocyanurate thermal insulation manufactured with HCFC blowing agent. 1.6 When adopted by an authority having jurisdiction, codes that address fire properties in many applications regulate the use of the thermal insulation materials covered by this specification. Fire properties are controlled by job, project, or other specifications where codes or government regulations do not apply. 1.7 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. 1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
2. Referenced Documents (purchase separately) ASTM Standards ASTM C165 Test Method for Measuring Compressive Properties of Thermal Insulations ASTM C168 Terminology Relating to Thermal Insulation ASTM C177 Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Guarded-Hot-Plate Apparatus ASTM C272 Test Method for Water Absorption of Core Materials for Structural Sandwich Constructions ASTM C303 Test Method for Dimensions and Density of Preformed Block and Board-Type Thermal Insulation ASTM C335 Test Method for Steady-State Heat Transfer Properties of Pipe Insulation ASTM C390 Practice for Sampling and Acceptance of Thermal Insulation Lots ASTM C411 Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation ASTM C518 Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus ASTM C550 Test Method for Measuring Trueness and Squareness of Rigid Block and Board Thermal Insulation ASTM C585 Practice for Inner and Outer Diameters of Thermal Insulation for Nominal Sizes of Pipe and Tubing ASTM C871 Test Methods for Chemical Analysis of Thermal Insulation Materials for Leachable Chloride, Fluoride, Silicate, and Sodium Ions ASTM C1045 Practice for Calculating Thermal Transmission Properties Under Steady-State Conditions ASTM C1058 Practice for Selecting Temperatures for Evaluating and Reporting Thermal Properties of Thermal Insulation ASTM C1114 Test Method for Steady-State Thermal Transmission Properties by Means of the Thin-Heater Apparatus ASTM C1303 Test Method for Predicting Long-Term Thermal Resistance of Closed-Cell Foam Insulation ASTM C1363 Test Method for Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus ASTM D883 Terminology Relating to Plastics ASTM D1621 Test Method for Compressive Properties of Rigid Cellular Plastics ASTM D1622 Test Method for Apparent Density of Rigid Cellular Plastics ASTM D2126 Test Method for Response of Rigid Cellular Plastics to Thermal and Humid Aging ASTM D2856 Test Method for Open-Cell Content of Rigid Cellular Plastics by the Air Pycnometer ASTM D6226 Test Method for Open Cell Content of Rigid Cellular Plastics ASTM E84 Test Method for Surface Burning Characteristics of Building Materials ASTM E96/E96M Test Methods for Water Vapor Transmission of Materials Index Terms cellular plastic; polyisocyanurate; polyurethane modified polyisocyanurate; thermal insulation; Cellular thermal insulation--specifications; Polyisocyanurate insulation; Preformed thermal insulation--specifications; Rigid thermal insulation--specifications; Thermal insulating materials--specifications; Unfaced thermal insulation—specifications
更多防火阻燃测试认证,请咨询中国防火网 电话:400-666-7290 网址:www.firete.com 邮箱:info@firete.com
...
|