NFPA 269 STANDARD TEST METHOD FOR DEVELOPING TOXIC POTENCY DATA FOR USE IN FIRE HAZARD MODELING NFPA 269 火灾模型用毒性数据的标准测试方法
1.1* Scope. 1.1.1 This test method is intended to provide a means for assessing the lethal toxic potency of combustion products produced from a material or product ignited when exposed to a radiant flux. 1.1.2 This test method has been designed to generate toxic potency data on materials and products (including composites) for use in fire hazard analysis. It is also permitted to be used to assist in the research and development of materials and products. 1.1.3 Lethal toxic potency values associated with 30-minute exposures are predicted using calculations that employ combustion atmospheric analytical data for carbon monoxide, carbon dioxide, oxygen (vitiation), and, if present, hydrogen cyanide, hydrogen chloride, and hydrogen bromide. The calculation method is therefore limited to those materials and products whose smoke toxicity can be attributed to these toxicants. 1.1.4 Specimens are exposed to a radiant heating flux with an electric spark ignition. 1.1.5 Specimens tested are representative of finished products, including composite and combination systems. 1.1.6 This standard is not intended to address all safety issues associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and to determine the applicability of regulatory limitations (especially with regard to the institutional care and use of experimental test animals) prior to use. (For specific hazard requirements, see Section 6.1.) Create fire protection solutions based on accurate data with NFPA 269. Vital for the development of data for use in toxic hazard modeling, NFPA 269 provides a means for assessing the lethal toxic potency of combustion products produced from a material or product ignited when exposed to a radiant flux. The test method provides toxic potency data on materials and products (including composites) for use in fire hazard analysis as well as product research and development. Completely reorganized for clarity and consistency with NFPA?'s Manual of Style, the 2007 NFPA 269 provides information on · Test method · Test apparatus · Hazards · Equipment calibration · Calculation · Analysis · Precision and bias (Softbound, 25 pp., 2007)
更多防火阻燃测试认证,请咨询中国防火网 电话:400-666-7290 网址:www.firete.com 邮箱:info@firete.com
... |