防火网
本站  
设为首页 加入收藏 网站地图   中文版 繁体 English
 
测试服务: 机车材料防火测试 | 建筑产品防火测试 | 船舶防火测试 | 飞机防火测试 | 耐火测试 | 喷射火测试 | 其他测试
   
用户名:
密码:
验证码:
   
 
主要阻燃防火认证标准
火车船舶汽车建材
 
相关测试方法 更多>>
EN ISO 9239-1:2010地
EN ISO 1182:2010
NF P 92-501
NF P 92-507
法标F级测试
法标I级测试
法国M级测试
EN ISO 1182
EN ISO 9239-1
EN 13501-1
 
首页   英国   BS EN 50265-2-1电缆单根垂直火焰燃烧测试
 

BS EN 50265-2-1电缆单根垂直火焰燃烧测试

BS EN 50265-2-1:1999 Common test methods for cables under fire conditions-test for resistance to vertical flame propagation for single insulated conductor or cable-Part 2-1: Procedures-1KW pre-mixed flame 在燃烧情况下电缆和绝缘导线性能的一般测试方法-单根电缆的垂直火焰蔓延测试,2-1部分:程度-1kw混合火焰.

 

This British Standard is the English language version of EN 50265-2-1:1999. When used in conjunction with BS EN 50265-1, it supersedes BS 4066-1:1980 which is withdrawn.

The standard is similar with DIN EN 60332-1-2, GB/T18380.12

 

Sample

The test sample shall be a piece of single insulated conductor or cable (600± 25)mm long.

The flame shall be applied continuously for the period of time corresponding to the diameter shown in Table 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaluation of test results

The single insulated conductor or cable shall pass the test if the distance between the lower edge of the top support and the onset of charring is greater than 50 mm.

 

In addition, a failure shall be recorded if charring extends downwards to a point greater than 540 mm from the lower edge of the top support.

 

If a failure is record, two more tests shall be carried out ,if both tests result in passes, the single insulated conductor or cable shall be deemed to have passed the test.

 

更多电缆单根燃烧测试,请联系中国防火网

 

全国免费咨询电话: 400-666-7290


 来源:防火网 发布时间:11/5/2014 点击次数:6112

 上一条: BS EN 1177:1998---游乐场地表面冲击减震—安全要求及测试方法

 下一条: 地板结构/地板覆盖物/地板布/地板构件BS 6853整体性测试
 
 
网站首页 | 测试服务 | 各国标准 | 新闻资讯 | 防火材料 | 会展信息 | 认证服务 | 在线咨询 | 联系我们
Copyright © 2009-2024 Firete.com All Right Reserved 苏公网安备 32010502010088号
服务热线:025-86583475   备案号:苏ICP备10201999号-1 DIN5510-2 DIN5510 防火网博客