BS 8434-1 Methods of test for assessment of the fire integrity of electric cables - Part 1: Test for unprotected small cables for use in emergency circuits-BS EN 50200 with addition of water spray BS 8434-1 电缆防火完整性评估的测试方法。第1部分:应急电路中使用的未保护小电缆的测试-BS EN 50200外加喷水器。
BS 8434-2 Methods oftest for assessment of the fire integrity of electric cables - Part 2: Test for unprotected small cables for use in emergency circuits- BS EN 50200 with a 930 °Cflame and with water spray BS 8434-2 电缆防火完整性评估的测试方法,第2部分:应急电路中使用的无防护型小电缆的测试-BS EN 50200外加930°C火焰和喷水器。
BS EN 50200, Method of test for resistance to fire of unprotected small cables for use in emergency circuits. BS EN 50200,应急电路中未保护的小电缆的防火性测试方法。
√ BS 8434-2电缆着火条件完整性-标准适用范围
BS 8434-2该标准规定了一种用于小型无保护电缆的测试方法,其中BS EN 50200的要求被修改为使用(930+40)C的火焰温 度和喷水的应用。使用此方法证明符合BS 5839-1要求。 This British Standard specifies a method of test to be used for small unprotected cables where the requirements of BS EN 50200 are modified to use a flame temperature of (930+40)'C and the application of water spray. Compliance with the requirements of BS 5839-1:2002, 26.2e) may be demonstrated using this method
√ BS EN 50200紧急电路用无保护小电缆的耐火性试验方法
EN 50200定义了用于应急电路的无保护小电缆(最大20mm)的耐火性测试方法。测试方法为在实验室中安装长度为1200mm的电缆样品,测试期间线芯的标称值为施加电压,从而产生闭合电路。 在测试期间,电缆在常规温度842°Cand机械冲程下经受特定时间段的火焰作用。 电缆正常运行的测量时间对应于所谓的耐火等级PH,这在标准NP-B-02851-1中也有提到 - 建筑构件的耐火试验(外径不大的细线的试验方法) 小于20毫米)。
√ BS EN 50200测试持续时间以分钟表示,并记录在以下分类中
PH 15: Flame exposure for 15 minutes PH 30: Flame exposure for 30 minutes PH 60: Flame exposure for 60 minutes PH 90: Flame exposure for 90 minutes PH 120: Flame exposure for 120 minutes
EN 50200附录E还有喷水(火灾,机械冲击和喷水),这是引用BS 8434-1标准的。 EN 50200与IEC 60331-2类似。与BS 6387不同的是,EN 50200测试同一根样品,同时受到火焰作用、机械冲击和水喷雾的应力。