DIN EN 50266-2-4多根电缆成束垂直火焰燃烧测试
DIN EN 50266-2-4:2001: Common test methods for cable under fire condition—Test for vertical flame spread of vertically-mounted bunched wires or cables –Part 2-5: Procedures –Category C
DIN EN 50266-2-4:2001: 着火条件下电缆的通用试验方法--多根成束垂直火焰燃烧--第2-5部分--类型C
EN 50266-2-4 together with BS EN 50266-1, EN 50266-2-1, EN 50266-2-2, EN 50266-2-3 and EN 50266-2-5, it supersedes BS 4066-3:1994 which is withdrawn
DIN 50266-2-4 类型C 是针对电缆直径大于等于12mm的测试,整个测试时间为20分钟。样品的前端固定。
根据样品燃烧后的破坏长度来评估样品是否通过DIN EN 50266-2-4此项测试。
DIN 5510-2:2009-05电缆燃烧性能测试的评定
根据DIN EN 50266-2-4电缆燃烧后的测试结果来评定电缆是否达到DIN 5510-2-2:2009-05的要求。
电线电缆其它标准 :
EN 50266-1 common test methods for cables under fire conditions—Test for vertical flame spread of vertically-mounted bunched wired or cables-Part 1: apparatus. 着火条件下电缆的通用试验方法--多根成束垂直火焰燃烧--第1部分—设备装置
EN 50266-2-5:2001: Common test methods for cable under fire condition—Test for vertical flame spread of vertically-mounted bunched wires or cables –Part 2-5: Procedures –Small cables-Category D 着火条件下电缆的通用试验方法--多根成束垂直火焰燃烧--第2-5部分--小型电缆--类型D
DIN EN 50266-2-4:电线电缆多根成束垂直火焰燃烧(电缆直径≥12mm),需要进行此测试的电缆和导线(不包括数据线),燃烧测试后电缆的最大破坏长度不超过2.5m.
DIN EN 50305 section 9.1.1: 电线电缆多根成束垂直火焰燃烧(6mm<电缆直径<12mm) 需要进行此测试的电缆和导线(不包括数据线),燃烧测试后电缆的最大破坏长度不超过2.5m.
DIN EN 50305 section 9.1.2: 电线电缆多根成束垂直火焰燃烧(电缆直径≤6mm 需要进行此测试的电缆和导线(不包括数据线),燃烧测试后电缆的最大破坏长度不超过2.5m.
DIN EN 60332-1-2:电线电缆单根垂直火焰燃烧,需要进行此测试的电缆和导线,包括数据线(光纤电缆、数据总线导线、同轴电缆),燃烧测试后,电缆的上端破坏长度不超过50mm,下端不超过540mm.
中国防火网免费咨询电话: 400-666-7290
|