Home station  
Set as homepage Add to favorites    中文版 繁体 English
 
Testing to: Rolling Fire testing | Building Fire testing | Marine material | Aircraft material | Fire Resistance | Jet Fire | Other
Company logo
Contact Information
Contact:Ms Li
Department:
Post:
Tel:025-86583035
Mobile:
Fax:
Email: info@firete.com
Add: No.118 Middle JiangdongRoad,Nanjing,Jiangsu,210012,China
Website: http://www.firete.com
Enterprise basic information
Type:
Business:
Number of employees:保密
 
Home About Products Business
 Location:Home > Firete.com > DIN EN 60332-1-2/DIN5510-2/Cable test
DIN EN 60332-1-2/DIN5510-2/Cable test
Release Date:2/24/2011  Hits:1944

DIN EN 60332-1-2/DIN5510-2/Cable test

DIN EN 60332-1-2:2004 vertical flame propagation for a single insulated wire or cable

DIN EN 60332-1-2:2004 Tests on electric and optical fibre cables under fire conditions—Part 1-2: Test for vertical flame propagation for a single insulated wire or cable—Procedure for 1 KW pre-mixed flame and is for general use, except that the procedure specified of less than 0.5mm2 total cross-section because the conductor melts before the test is completed, or for the testing of small optical fibre cables because the cable is broken before the test is completes. In these cases, the procedure giver in DIN EN IEC 60332-2-2 is recommended.

Description of test method

The test sample shall be a piece of single insulated conductor or cable (600± 25)mm long.

The single insulated conductor or cable shall pass the test if the distance between the lower edge of the top support and the onset of charring is greater than 50 mm.

In addition, a failure shall be recorded if charring extends downwards to a point greater than 540 mm from the lower edge of the top support.

If a failure is record, two more tests shall be carried out ,if both tests result in passes, the single insulated conductor or cable shall be deemed to have passed the test.

Other standard:

DIN EN 60332-2-2:2004 Tests on electric and optical fibre cables under fire conditions Part 2-2: Tests for vertical flame propagation for a single small insulated wire or cable procedure for diffusion flame.

Tel: 400-666-7290 4006667290